Exciter Model: AC3C
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0 < Te < Mult*TimeStep then Te = Mult*TimeStep
- If 0 < Tf < Mult*TimeStep then Tf = Mult*TimeStep
- If 0.0 < Ta < 0.5*Mult*TimeStep then Ta = 0, ElseIf 0.5*Mult*TimeStep < Ta < Mult*TimeStep then Ta = Mult*TimeStep
- If 0.0 < Tb < 0.5*Mult*TimeStep then Tb = 0, ElseIf 0.5*Mult*TimeStep < Tb < Mult*TimeStep then Tb = Mult*TimeStep
- If 0.0 < Tdr < 0.5*Mult*TimeStep then Tdr = 0, ElseIf 0.5*Mult*TimeStep < Tdr < Mult*TimeStep then Tdr = Mult*TimeStep
- If 0.0 < Tr < 0.25*Mult*TimeStep then Tr = 0.0
ElseIf 0.25*Mult*TimeStep < Tr < 0.5*Mult*TimeStep then Tr = 0.5*Mult*TimeStep - If Ka = 0 then Ka = Mult*TimeStep
- If Kr = 0 then Kr = Mult*TimeStep
- If Vamax < Vamin then swap the values
- If VPIDmax < VPIDmin then swap the values
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Va > Vamax, then Vamax = Va limits or if Va < Vamin, then Vamin = Va
- If Ve < Vfemin, then Vfemin = Ve limits
Model Equations and/or Block Diagrams
Parameters:
| OEL | OEL input: if = 2, LV gate; if < 2, subtract from error signal |
| UEL | UEL input: if = 2, HV gate; if < 2, add to error signal |
| SCL | SCL input: if = 2, LV gate; if < 2, subtract from error signal |
| Tr | Filter time constant, sec |
| Tb | Time constant, sec |
| Tc | Time constant, sec |
| Ka | Voltage regulator gain |
| Ta | Voltage regulator time constant, sec |
| VaMax | Maximum control element output, pu |
| VaMin | Minimum control element output, pu |
| Te | Exciter field time constant, sec |
| Vemin | Minimimum exciter output voltage, pu |
| Kr | Field voltage feedback gain, pu |
| Kf | Rate feedback gain, pu |
| Tf | Rate feedback constant, sec |
| Kn | High level rate feedback gain, pu |
| Efdn | Rate feedback gain break level, pu |
| Kc | Rectifier loading factor proportional to commutating reactance |
| Kd | Exciter internal reactance, pu |
| Ke | Exciter field resistance constant, pu |
| Vfemax | Exciter field current limit parameter, pu |
| E1 | Field voltage value, 1 |
| SE1 | Saturation factor at E1 |
| E2 | Field voltage value, 2 |
| SE2 | Saturation factor at E2 |
| Kpr | Proportional gain, pu |
| Kir | Integral gain, pu |
| Kdr | Regulator derivative gain, pu |
| Tdr | Derivative gain washout time constant, sec |
| Vpidmax | PID maximum limit |
| Vpidmin | PID minimum limit |
| Spdmlt | If not zero, multiply output (Efd) by generator speed |